Name
Values (Range)
Unit
Step
Default
Description
ResCrvType_OV1
Instantaneous
Frozen timer
Linearly decreased
-
-
Instantaneous
Selection of reset curve type for OV1
tResetDef_OV1
0.00 - 6000.00
s
0.01
0.00
Reset time delay in sec for definite time use
of OV1
tResetIDMT_OV1
0.00 - 6000.00
s
0.01
0.00
Reset time delay in sec for Inverse-Time
curves for OV1
A_OV1
0.005 - 999.000
-
0.001
0.140
Parameter A for customer programmable
curve for OV1
B_OV1
0.500 - 99.000
-
0.001
1.000
Parameter B for customer programmable
curve for OV1
C_OV1
0.000 - 1.000
-
0.001
1.000
Parameter C for customer programmable
curve for OV1
D_OV1
0.000 - 10.000
-
0.001
0.000
Parameter D for customer programmable
curve for OV1
P_OV1
0.001 - 10.000
-
0.001
0.020
Parameter P for customer programmable
curve for OV1
ResCrvType_OV2
Instantaneous
Frozen timer
Linearly decreased
-
-
Instantaneous
Selection of reset curve type for OV2
tResetDef_OV2
0.00 - 6000.00
s
0.01
0.00
Reset time delay in sec for definite time use
of OV2
tResetIDMT_OV2
0.00 - 6000.00
s
0.01
0.00
Reset time delay in sec for Inverse-Time
curves for OV2
A_OV2
0.005 - 999.000
-
0.001
0.140
Parameter A for customer programmable
curve for OV2
B_OV2
0.500 - 99.000
-
0.001
1.000
Parameter B for customer programmable
curve for OV2
C_OV2
0.000 - 1.000
-
0.001
1.000
Parameter C for customer programmable
curve for OV2
D_OV2
0.000 - 10.000
-
0.001
0.000
Parameter D for customer programmable
curve for OV2
P_OV2
0.001 - 10.000
-
0.001
0.020
Parameter P for customer programmable
curve for OV2
ResCrvType_UV1
Instantaneous
Frozen timer
Linearly decreased
-
-
Instantaneous
Selection of reset curve type for UV1
tResetDef_UV1
0.00 - 6000.00
s
0.01
0.00
Reset time delay in sec for definite time use
of UV1
tResetIDMT_UV1
0.00 - 6000.00
s
0.01
0.00
Reset time delay in sec for Inverse-Time
curves for UV1
A_UV1
0.005 - 999.000
-
0.001
0.140
Parameter A for customer programmable
curve for UV1
B_UV1
0.500 - 99.000
-
0.001
1.000
Parameter B for customer programmable
curve for UV1
Table continues on next page
Section 10
1MRK505222-UUS C
Multipurpose protection
592
Technical reference manual
Summary of Contents for Relion 670 series
Page 1: ...Relion 670 series Line differential protection RED670 ANSI Technical reference manual...
Page 2: ......
Page 40: ...34...
Page 50: ...44...
Page 60: ...54...
Page 126: ...120...
Page 384: ...378...
Page 496: ...490...
Page 556: ...550...
Page 602: ...596...
Page 620: ...614...
Page 794: ...788...
Page 864: ...858...
Page 988: ...982...
Page 998: ...992...
Page 1084: ...1078...
Page 1164: ...1158...
Page 1168: ...1162...
Page 1220: ...1214...
Page 1230: ...1224...
Page 1231: ...1225...