11.2.5
Setting parameters
Table 313:
SDDRFUF Group settings (basic)
Name
Values (Range)
Unit
Step
Default
Description
Operation
Disabled
Enabled
-
-
Enabled
Disable/Enable Operation
IBase
1 - 99999
A
1
3000
Base current
VBase
0.05 - 2000.00
kV
0.05
400.00
Base voltage
OpModeSel
Disabled
V2I2
V0I0
V0I0 OR V2I2
V0I0 AND V2I2
OptimZsNs
-
-
V0I0
Operating mode selection
3V0PU
1 - 100
%VB
1
30
Pickup of residual overvoltage element in %
of VBase
3I0PU
1 - 100
%IB
1
10
Pickup of residual undercurrent element in %
of IBase
3V2PU
1 - 100
%VB
1
30
Pickup of negative sequence overvoltage
element in % of VBase
3I2PU
1 - 100
%IB
1
10
Pickup of negative sequence undercurrent
element in % of IBase
OpDVDI
Disabled
Enabled
-
-
Disabled
Operation of change based function Disable/
Enable
DVPU
1 - 100
%VB
1
60
Pickup of change in phase voltage in % of
VBase
DIPU
1 - 100
%IB
1
15
Pickup of change in phase current in % of
IBase
VPPU
1 - 100
%VB
1
70
Pickup of phase voltage in % of VBase
IPPU
1 - 100
%IB
1
10
Pickup of phase current in % of IBase
SealIn
Disabled
Enabled
-
-
Enabled
Seal in functionality Disable/Enable
VSealInPU
1 - 100
%VB
1
70
Pickup of seal-in phase voltage in % of VBase
IDLDPU
1 - 100
%IB
1
5
Pickup for phase current detection in % of
IBase for dead line detection
VDLDPU
1 - 100
%VB
1
60
Pickup for phase voltage detection in % of
VBase for dead line detection
Section 11
1MRK505222-UUS C
Secondary system supervision
612
Technical reference manual
Summary of Contents for Relion 670 series
Page 1: ...Relion 670 series Line differential protection RED670 ANSI Technical reference manual...
Page 2: ......
Page 40: ...34...
Page 50: ...44...
Page 60: ...54...
Page 126: ...120...
Page 384: ...378...
Page 496: ...490...
Page 556: ...550...
Page 602: ...596...
Page 620: ...614...
Page 794: ...788...
Page 864: ...858...
Page 988: ...982...
Page 998: ...992...
Page 1084: ...1078...
Page 1164: ...1158...
Page 1168: ...1162...
Page 1220: ...1214...
Page 1230: ...1224...
Page 1231: ...1225...