12.3.8.3
Function block
IEC05000339-2-en.vsd
SXSWI
BLOCK
LR_SWI
OPEN
CLOSE
BL_OPEN
BL_CLOSE
BL_UPD
POSOPEN
POSCLOSE
RS_CNT
XIN
XPOS
EXE_OP
EXE_CL
SUBSTED
OP_BLKD
CL_BLKD
UPD_BLKD
POSITION
OPENPOS
CLOSEPOS
CNT_VAL
L_CAUSE
IEC05000339 V2 EN
Figure 346:
SXSWI function block
12.3.8.4
Input and output signals
Table 341:
SXSWI Input signals
Name
Type
Default
Description
BLOCK
BOOLEAN
0
Block of function
LR_SWI
BOOLEAN
0
Local/Remote switch indication from switchyard
OPEN
BOOLEAN
0
Pulsed signal used to immediately open the switch
CLOSE
BOOLEAN
0
Pulsed signal used to immediately close the switch
BL_OPEN
BOOLEAN
0
Signal to block the open command
BL_CLOSE
BOOLEAN
0
Signal to block the close command
BL_UPD
BOOLEAN
0
Steady signal for block of the position updating
POSOPEN
BOOLEAN
0
Signal for open position of apparatus from I/O
POSCLOSE
BOOLEAN
0
Signal for close position of apparatus from I/O
RS_CNT
BOOLEAN
0
Resets the operation counter
XIN
BOOLEAN
0
Execution information from CSWI
Table 342:
SXSWI Output signals
Name
Type
Description
XPOS
GROUP SIGNAL
Group signal for XSWI output
EXE_OP
BOOLEAN
Executes the command for open direction
EXE_CL
BOOLEAN
Executes the command for close direction
SUBSTED
BOOLEAN
Indication that the position is substituted
OP_BLKD
BOOLEAN
Indication that the function is blocked for open
commands
Table continues on next page
Section 12
1MRK505222-UUS C
Control
680
Technical reference manual
Summary of Contents for Relion 670 series
Page 1: ...Relion 670 series Line differential protection RED670 ANSI Technical reference manual...
Page 2: ......
Page 40: ...34...
Page 50: ...44...
Page 60: ...54...
Page 126: ...120...
Page 384: ...378...
Page 496: ...490...
Page 556: ...550...
Page 602: ...596...
Page 620: ...614...
Page 794: ...788...
Page 864: ...858...
Page 988: ...982...
Page 998: ...992...
Page 1084: ...1078...
Page 1164: ...1158...
Page 1168: ...1162...
Page 1220: ...1214...
Page 1230: ...1224...
Page 1231: ...1225...