13.8.11.6
Technical data
Table 490:
LCP3TUC (37) technical data
Function
Range or value
Accuracy
Operate value,
undercurrent
(1.00-100.00)% of IBase
± 1.0% of I
n
Reset ratio, undercurrent
>105%
-
Operate time, start
20 ms typically at 2 to 0xI
set
-
Reset time, start
30 ms typically at 0 to 2xI
set
-
Critical impulse time,
undercurrent
10 ms typically at 2 to 0xI
set
-
Impulse margin time,
undercurrent
10 ms typically
-
Timers
(0.000-60.000) s
± 0.5% ± 10 ms
1MRK505222-UUS C
Section 13
Scheme communication
857
Technical reference manual