PulseTime
Output 1
PulseTime
Output 2
PulseTime
Output 3
Input 17
Input 32
Input 1
Input 16
OR
OR
OR
OR
AND
AND
ModeOutput1
OR
ModeOutput2
OR
ModeOutput3
t
t
t
ANSI10000055-1-en.vsd
AND
AND
AND
AND
0
0-OnDelay
0
0-OnDelay
0
0-OnDelay
0-OffDelay
0
0-OffDelay
0
0-OffDelay
0
ANSI10000055 V2 EN
Figure 434:
Trip matrix internal logic
Output signals from TMAGGIO are typically connected to other logic blocks or
directly to output contacts in the IED. When used for direct tripping of the circuit
breaker(s) the pulse time delay shall be set to approximately 0.150 seconds in order to
obtain satisfactory minimum duration of the trip pulse to the circuit breaker trip coils.