Actual value of the measured quantity
The actual value of the measured quantity is available locally and remotely. The
measurement is continuous for each measured quantity separately, but the reporting of
the value to the higher levels depends on the selected reporting mode. The following
basic reporting modes are available:
•
Cyclic reporting (
Cyclic
)
•
Magnitude dead-band supervision (
Dead band
)
•
Integral dead-band supervision (
Int deadband
)
Cyclic reporting
The cyclic reporting of measured value is performed according to chosen setting
(
XRepTyp
). The measuring channel reports the value independent of magnitude or
integral dead-band reporting.
In addition to the normal cyclic reporting the IED also report spontaneously when
measured value passes any of the defined threshold limits.
en05000500.vsd
V
a
lu
e
1
Y
t
V
a
lu
e
2
V
a
lu
e
3
V
a
lu
e
4
Value Reported
(1st)
Value Reported
V
a
lu
e
5
Value Reported
Y1
Y2
Y5
Value Reported
Value Reported
Y3
Y4
(*)Set value for t: XDbRepInt
t (*)
t (*)
t (*)
t (*)
IEC05000500 V1 EN
Figure 453:
Periodic reporting
1MRK505222-UUS C
Section 15
Monitoring
899
Technical reference manual
Summary of Contents for Relion 670 series
Page 1: ...Relion 670 series Line differential protection RED670 ANSI Technical reference manual...
Page 2: ......
Page 40: ...34...
Page 50: ...44...
Page 60: ...54...
Page 126: ...120...
Page 384: ...378...
Page 496: ...490...
Page 556: ...550...
Page 602: ...596...
Page 620: ...614...
Page 794: ...788...
Page 864: ...858...
Page 988: ...982...
Page 998: ...992...
Page 1084: ...1078...
Page 1164: ...1158...
Page 1168: ...1162...
Page 1220: ...1214...
Page 1230: ...1224...
Page 1231: ...1225...