user must use a PC and - either the PCM600 Disturbance handling tool - or a FTP or
MMS (over 61850) client. The PC can be connected to the IED front, rear or remotely
via the station bus (Ethernet ports).
Indications (IND)
Indications is a list of signals that were activated during the total recording time of the
disturbance (not time-tagged), see section
for more detailed information.
Event recorder (ER)
The event recorder may contain a list of up to 150 time-tagged events, which have
occurred during the disturbance. The information is available via the local HMI or
PCM600, see section
for more detailed information.
Sequential of events (SOE)
The sequetial of events may contain a list of totally 1000 time-tagged events. The list
information is continuously updated when selected binary signals change state. The
oldest data is overwritten. The logged signals may be presented via local HMI or
PCM600, see section
for more detailed information.
Trip value recorder (TVR)
The recorded trip values include phasors of selected analog signals before the fault and
during the fault, see section
for more detailed information.
Disturbance recorder (DR)
Disturbance recorder records analog and binary signal data before, during and after the
fault, see section
for more detailed information.
Fault locator (FL)
The fault location function calculates the distance to fault, see section
for more detailed information.
Time tagging
The IED has a built-in real-time calendar and clock. This function is used for all time
tagging within the disturbance report
Recording times
Disturbance report DRPRDRE records information about a disturbance during a
settable time frame. The recording times are valid for the whole disturbance report.
Disturbance recorder (DR), event recorder (ER) and indication function register
disturbance data and events during tRecording, the total recording time.
The total recording time, tRecording, of a recorded disturbance is:
tRecording =
PreFau PostFaultrecT or PreFau TimeLimit, depending on
which criterion stops the current disturbance recording
1MRK505222-UUS C
Section 15
Monitoring
953
Technical reference manual
Summary of Contents for Relion 670 series
Page 1: ...Relion 670 series Line differential protection RED670 ANSI Technical reference manual...
Page 2: ......
Page 40: ...34...
Page 50: ...44...
Page 60: ...54...
Page 126: ...120...
Page 384: ...378...
Page 496: ...490...
Page 556: ...550...
Page 602: ...596...
Page 620: ...614...
Page 794: ...788...
Page 864: ...858...
Page 988: ...982...
Page 998: ...992...
Page 1084: ...1078...
Page 1164: ...1158...
Page 1168: ...1162...
Page 1220: ...1214...
Page 1230: ...1224...
Page 1231: ...1225...