Setting example with two transformers in the protected zone (master-
slave differential operation)
IEC13000295-2-en.vsdx
A
B
C
T
B
T
A
IED
IED
IED
IEC13000295 V2 EN-US
Figure 39: Master- slave differential operation
Setting
Station A
Station B
Station C
PDIF
L3TCPDIF
NoOfUsedCTs
3
TraAOnInpCh
2
TraBOnInpCh
3
Protection functions in stations B and C operate as slaves (differential function switched off)
so currents are sent to protection function in station A, and received on channels 2 and 3. To
inform the differential algorithm that currents are coming from the LV sides of the
transformers,
TraAOnInpCh must be set to 2 and TraBOnInpCh to 3 (channel1 is reserved for
local measurement). This is to ensure that proper turn ratio and vector group correction is
done.
Setting example with a three-winding transformer in the protected zone
IEC13000296-1-en.vsdx
IED
IED
A
B
T
T
IEC13000296 V2 EN-US
Figure 40: Three-winding transformer in the zone
1MRK 505 382-UEN E
Section 4
Analog and binary signal transfer for line differential protection
Communication set-up, 670/650 series
39
Application Guide
© Copyright 2017 ABB. All rights reserved