4.8.2
Configuration of binary inputs and outputs
GUID-89D944D1-DD6C-4666-8AA6-38FE5F366095 v1
GUID-0918C53D-F755-4FA1-BB3C-F672AFC6A7D2 v1
Signals are available in the Signal Matrix Tool (SMT) and as hardware channels
in the Application Configuration Tool (ACT).
4.8.2.1
Configuration of binary inputs and outputs via ACT
GUID-7102E264-F540-434C-96BA-47E72DA665B2 v1
LDCM hardware channels can be connected via ACT by right-clicking on the chosen connection
point, and then selecting Connect/Hardware Channel (see Figure
IEC10000241 V1 EN-US
Figure 46: Configuration of binary inputs and outputs via ACT
If an installed LDCM is not used, it should be removed or set to binary mode
without any connections, or the
ChannelMode parameter should be set to
Blocked. Otherwise parallel LDCMs may get blocked.
The following can be done in the Hardware Channel Allocation dialog:
•
Hardware Module selection
•
Hardware Channel selection
•
User Defined Name for the channel
IEC10000242-1-en.vsdx
IEC10000242 V1 EN-US
Figure 47: Hardware Channel Allocation dialog
1MRK 505 382-UEN E
Section 4
Analog and binary signal transfer for line differential protection
Communication set-up, 670/650 series
45
Application Guide
© Copyright 2017 ABB. All rights reserved
Summary of Contents for Relion 670 series
Page 1: ...Relion 670 650 SERIES Communication set up 670 650 series Version 2 2 Application Guide...