GUID-4CBDD9D5-E3B1-4FD8-A510-9BD5363BACD1 v1
IEC07000235-1-en.vsdx
AsymDelay
at end A is set to 3 ms - 2 ms = 1 ms
AsymDelay
at end B is set to 2 ms - 3 ms = -1 ms
2 ms delay
1 ms delay
2 ms delay
Tx
Rx
Tx
Rx
A
B
C*
*The 3 ms delay in route A-C-B includes the delay in the multiplexer at end C.
IED
IED
IEC07000235 V1 EN-US
Figure 56: Setting example for AsymDelay
4.8.5
Settings
IP14245-1 v2
PID-6471-SETTINGS v2
Table 14: LDCMRecBinStat1 Non group settings (basic)
Name
Values (Range)
Unit
Step
Default
Description
ChannelMode
Blocked
Normal
OutOfService
-
-
Normal
Channel mode of LDCM
TerminalNo
0 - 255
-
1
0
Terminal number used for line
differential communication
RemoteTermNo
0 - 255
-
1
0
Terminal number on remote terminal
CommSync
Slave
Master
-
-
Slave
Com Synchronization mode of LDCM
OptoPower
LowPower
HighPower
-
-
LowPower
Transmission power for LDCM
ComAlarmDel
5 - 10000
ms
5
100
Time delay before communication
alarm signal is activated
ComAlrmResDel
5 - 10000
ms
5
100
Reset delay before communication
alarm signal is reset
PID-6472-SETTINGS v2
Table 15: LDCMRecBinStat2 Non group settings (basic)
Name
Values (Range)
Unit
Step
Default
Description
ChannelMode
Blocked
Normal
OutOfService
-
-
Normal
Channel mode of LDCM
TerminalNo
0 - 255
-
1
0
Terminal number used for line
differential communication
RemoteTermNo
0 - 255
-
1
0
Terminal number on remote terminal
DiffSync
Echo
GPS
-
-
Echo
Diff Synchronization mode of LDCM
Table continues on next page
Section 4
1MRK 505 382-UEN E
Analog and binary signal transfer for line differential protection
56
Communication set-up, 670/650 series
Application Guide
© Copyright 2017 ABB. All rights reserved