Name
Values (Range)
Unit
Step
Default
Description
DeadbandtDiff
200 - 1000
us
1
300
Deadband for t Diff
LinkForwarded
Off
LDCM305
LDCM306
LDCM312
LDCM313
LDCM322
LDCM323
-
-
Off
Link forwarded from other LDCM
RedundantCh
Off
On
-
-
Off
Redundant channel enabled
GUID-9EAC68A3-1186-42B0-860C-119B414F615A v1
ComAlarmDel should be set to ≥ 100 ms in normal service. Route switching in
telecommunication networks takes usually < 50 ms.
ComAlrmResDel should be
set to 10 ms. It may be advantageous to set
ComAlrmResDel to 5 - 10 ms for
fault tracing.
Section 4
1MRK 505 382-UEN E
Analog and binary signal transfer for line differential protection
60
Communication set-up, 670/650 series
Application Guide
© Copyright 2017 ABB. All rights reserved