PCM
Pulse code multiplexer
5.4.5.1
Service settings for the line differential protection IED with X.21 galvanic
interface
GUID-66F9DFE3-3D64-4CDB-97D8-19D13F56EA55 v2
X.21 Micro D-sub 15–pole male connector according to V11 (X:27) balanced version is used for
X.21 communication.
5.4.5.2
PDH telecommunication via C37.94 interface to external transceiver
C37.94-X.21
GUID-65BB5DA1-51AC-45CA-A482-FE0EB48CB622 v1
When the distance between IED and PCM equipment is more than 10 meters and an X.21
interface on the PCM needs to be used, it can be accomplished by using an external converter
from C37.94 to X.21.
LOCAL
REMOTE
< 10 m
IED
C37.94
C37.94/X.21
converter
PCM
Multi-mode
fibre-optic
< 3 km
Galvanic
connection
interface
G.703
Internal clock
(master)
External clock
(slave)
External clock
IEC18000099-1-en.vsdx
IED
C37.94
< 10 m
PCM
(slave)
Galvanic
connection
interface
G.703
Multi-mode
fibre-optic
< 3 km
C37.94/X.21
converter
IEC18000099 V1 EN-US
Figure 68: PDH Communication structure using PCM with X.21
Contact your local ABB representative for more details about C37.94 to X.21
converters.
5.5
PDH telecommunication via C37.94 interface to
transceiver 21-216
5.5.1
Communication requirements
GUID-1BF17CA3-93F5-4661-9695-368FE7F359E2 v1
A PDH telecommunication network set-up can be done via 64 kbit/s C37.94 interface to
transceiver type 21-216.
There is a short delay in alarm time, typically 100 ms, for a communication fail in the relay, and
it is derived from the dependability of the line differential protection function. This requires a
high quality communication system as defined in Appendix
Section 5
1MRK 505 382-UEN E
Communication set-up
70
Communication set-up, 670/650 series
Application Guide
© Copyright 2017 ABB. All rights reserved