LOCAL
REMOTE
< 10 m
IED
Transceiver
21-219
SDH
MUX
IED
Multi-mode
fibre-optic
< 3.5 km
Galvanic
connection
interface
G.703 E1
(2Mbit)
SDH
master
Slaves
Slaves (external clock)
IEC07000156-1-en.vsdx
G.704 (framed etc.)
< 10 m
SDH
MUX
Multi-mode
fibre-optic
< 3.5 km
Galvanic
connection
interface
G.703 E1
(2Mbit)
Transceiver
21-219
IEC07000156 V1 EN-US
Figure 79: Communication structure with transceiver 21-219 port synchronized from SDH
master clock
IED
Terminal used for binary signal transfer
Transceiver 21–219
Optical-to-electrical interface converter
SDH MUX
SDH multiplexer
5.6.3
Communication structure with PDH/SDH port synchronized
from transceiver 21-219
GUID-59042A8F-D4CA-41AA-A4B6-17B6A99E199A v1
Setting up a PDH telecommunication network requires that synchronization is provided from
an external source, for example, from one transceiver 21-219 (see Figure
). The SDH
multiplexer (SDH MUX) is thus set not to interfere with synchronization. This requirement is
usually fulfilled by setting the SDH MUX to transparent mode.
Section 5
1MRK 505 382-UEN E
Communication set-up
78
Communication set-up, 670/650 series
Application Guide
© Copyright 2017 ABB. All rights reserved