Test 2 to Test n: loop back RX+ to TX+ and RX- to TX-. Loop back, one-by-one, in respective
interface in the communication network. Check that the communication status is OK for each
interface point on the local HMI. If no fault is found, Test 1 and Test 2 should be repeated in
reverse order from the remote end.
When loop-back testing is finished, remember to restore the original terminal
numbers. Having the same terminal number at both ends can cause an
unwanted trip. If the terminal was set to Test mode, check that the local trip is
reset before leaving the Test mode
Section 5
1MRK 505 382-UEN E
Communication set-up
90
Communication set-up, 670/650 series
Application Guide
© Copyright 2017 ABB. All rights reserved