5.5.5.2
Service settings for transceiver 21–216
GUID-4B6CB0C7-8F0E-4FE8-BD12-A3E03FE4FF72 v1
IEC07000256 V1 EN-US
Figure 75: Transceiver 21–216
Only one setting is required for transceiver 21–216. It has to be set to external clock. Rotary
switch on the front panel pointing to position 0 indicates that external clock is selected. If
back-to-back testing is to be performed, one transceiver 21-216 has to be set as master by
setting the rotary switch to position 2 (overrides settings of jumpers 8 and 9). Clock
synchronization configuration using the rotary switch can be done on the fly.
5.5.6
Earthing
GUID-F03C51FF-418F-4761-BF4C-73833D10804D v1
The recommended earthing method is direct earthing. With earth loop problems, soft earth
method can be beneficial (see Figures
and
).