The R1 and jX1 in figure
represents the positive sequence impedance from the
measuring point to the fault location. The RFPG is presented in order to “convey” the
fault resistance reach.
The zone may be set to operate in , ,
Disabled
or direction through the setting
OperationDir
. The result from respective set value is illustrated in figure
be convenient to once again mention that the impedance reach is symmetric, in the
sense that it is conform for forward and reverse direction. Therefore, all reach settings
apply to both directions.
en05000182.vsd
R
X
R
X
R
X
Non-directional
Forward
Reverse
IEC05000182 V1 EN
Figure 134:
Directional operating modes of the distance measuring zone
6.5.2.3
Minimum operating current
The operation of the distance measuring zone is blocked if the magnitude of input
currents fall below certain threshold values.
The phase-to-ground loop AG (BG or CG) is blocked if IA (IB or IC) <
IMinPUPG
.
For zone 1 with load compensation feature the additional criterion applies, that all phase-
to-ground loops will be blocked when IN <
IMinOpIR
, regardless of the phase currents.
IA (IB or IC) is the RMS value of the current in phase IA (IB or IC). IN is the RMS
value of the vector sum of the three phase currents, that is, residual current 3I0.
1MRK505222-UUS C
Section 6
Impedance protection
265
Technical reference manual
Summary of Contents for Relion 670 series
Page 1: ...Relion 670 series Line differential protection RED670 ANSI Technical reference manual...
Page 2: ......
Page 40: ...34...
Page 50: ...44...
Page 60: ...54...
Page 126: ...120...
Page 384: ...378...
Page 496: ...490...
Page 556: ...550...
Page 602: ...596...
Page 620: ...614...
Page 794: ...788...
Page 864: ...858...
Page 988: ...982...
Page 998: ...992...
Page 1084: ...1078...
Page 1164: ...1158...
Page 1168: ...1162...
Page 1220: ...1214...
Page 1230: ...1224...
Page 1231: ...1225...