reverse direction. The zone measurement function filter out the relevant signals on the
DIRCND input depending on the setting of the parameter
OperationDir
. It shall be
configured to the DIRCND output on the Directional impedance element for mho
characteristic (ZDMRDIR,21D) function.
en06000408_ansi.vsd
AND
AND
AND
AG
BG
CG
PHSEL
NDIR_A
NDIR_B
NDIR_C
NDIR_G
AND
BLOCK
LOVBZ
PHPUND
BLK
OR
OR
OR
ANSI06000408 V1 EN
Figure 136:
Conditioning by a group functional input signal PHSEL
Composition of the phase pickup signals for a case, when the zone operates in a non-
directional mode, is presented in figure
en06000409_ansi.vsd
NDIR_A
NDIR_B
NDIR_C
OR
AND
AND
AND
AND
BLK
PICKUP
PU_C
PU_B
PU_A
15 ms
0
15 ms
0
15 ms
0
15 ms
0
ANSI06000409 V1 EN
Figure 137:
Composition of pickup signals in non-directional operating mode
1MRK505222-UUS C
Section 6
Impedance protection
271
Technical reference manual