There is an operation mode (
OpModeSel
) setting:
1 out of 3
or
2 out of 3
. If the
parameter is set to
1 out of 3
any phase trip signal will be activated. If the parameter is
set to
2 out of 3
at least two phase signals must be activated for trip.
There is also a possibility to activate a preset change of the set operation current
(MultPU)
via a binary input (MULTPU). In some applications the operation value
needs to be changed, for example due to transformer inrush currents.
PHPIOC (50) can be blocked from the binary input BLOCK.
7.1.3
Function block
ANSI04000391-2-en.vsd
PHPIOC (50)
I3P*
BLOCK
MULTPU
TRIP
TR_A
TR_B
TR_C
ANSI04000391 V2 EN
Figure 200:
PHPIOC (50) function block
7.1.4
Input and output signals
Table 184:
PHPIOC (50) Input signals
Name
Type
Default
Description
I3P
GROUP
SIGNAL
-
Three phase current
BLOCK
BOOLEAN
0
Block of function
MULTPU
BOOLEAN
0
Enable current pickup value multiplier
Table 185:
PHPIOC (50) Output signals
Name
Type
Description
TRIP
BOOLEAN
Trip signal from any phase
TR_A
BOOLEAN
Trip signal from phase A
TR_B
BOOLEAN
Trip signal from phase B
TR_C
BOOLEAN
Trip signal from phase C
Section 7
1MRK505222-UUS C
Current protection
380
Technical reference manual
Summary of Contents for Relion 670 series
Page 1: ...Relion 670 series Line differential protection RED670 ANSI Technical reference manual...
Page 2: ......
Page 40: ...34...
Page 50: ...44...
Page 60: ...54...
Page 126: ...120...
Page 384: ...378...
Page 496: ...490...
Page 556: ...550...
Page 602: ...596...
Page 620: ...614...
Page 794: ...788...
Page 864: ...858...
Page 988: ...982...
Page 998: ...992...
Page 1084: ...1078...
Page 1164: ...1158...
Page 1168: ...1162...
Page 1220: ...1214...
Page 1230: ...1224...
Page 1231: ...1225...