Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Four step phase overcurrent protection
OC4PTOC
4
4
alt
3I>
TOC-REVA V1 EN
51/67
7.2.1
Introduction
The four step phase overcurrent protection function OC4PTOC (51/67) has
independent inverse time delay settings for step 1 and 4. Step 2 and 3 are always
definite time delayed.
All IEC and ANSI inverse time characteristics are available together with an optional
user defined time characteristic.
The directional function is voltage polarized with memory. The function can be set to
be directional or non-directional independently for each of the steps.
Second harmonic blocking level can be set for the function and can be used to block
each step individually
7.2.2
Principle of operation
The Four step phase overcurrent protection OC4PTOC (51/67) is divided into four
different sub-functions, one for each step. For each step
x
, where x is step 1, 2, 3 and
4, an operation mode is set by
DirModeSelx
:
Disable
/
Non-directional
/
Forward
/
Reverse
.
The protection design can be decomposed in four parts:
•
The direction element
•
The harmonic Restraint Blocking function
•
The four step over current function
•
The mode selection
If VT inputs are not available or not connected, setting parameter
DirModeSelx
shall be left to default value,
Non-directional
.
Section 7
1MRK505222-UUS C
Current protection
382
Technical reference manual
Summary of Contents for Relion 670 series
Page 1: ...Relion 670 series Line differential protection RED670 ANSI Technical reference manual...
Page 2: ......
Page 40: ...34...
Page 50: ...44...
Page 60: ...54...
Page 126: ...120...
Page 384: ...378...
Page 496: ...490...
Page 556: ...550...
Page 602: ...596...
Page 620: ...614...
Page 794: ...788...
Page 864: ...858...
Page 988: ...982...
Page 998: ...992...
Page 1084: ...1078...
Page 1164: ...1158...
Page 1168: ...1162...
Page 1220: ...1214...
Page 1230: ...1224...
Page 1231: ...1225...