Pickup1
PU_ST1
TRST1
tReset1
t1
ANSI10000040-3-en.vsd
ANSI10000040 V3 EN
Figure 253:
Example for Definite Time Delay stage1 operation
8.1.2.3
Blocking
It is possible to block Two step undervoltage protection UV2PTUV (27) partially or
completely, by binary input signals or by parameter settings, where:
BLOCK:
blocks all outputs
BLKTR1:
blocks all trip outputs of step 1
BLK1:
blocks all pickup and trip outputs related to step 1
BLKTR2:
blocks all trip outputs of step 2
BLK2:
blocks all pickup and trip outputs related to step 2
If the measured voltage level decreases below the setting of
IntBlkStVal1
, either the
trip output of step 1, or both the trip and the PICKUP outputs of step 1, are blocked.
The characteristic of the blocking is set by the
IntBlkSel1
parameter. This internal
blocking can also be set to
Disabled
resulting in no voltage based blocking.
Corresponding settings and functionality are valid also for step 2.
In case of disconnection of the high voltage component the measured voltage will get
very low. The event will PICKUP both the under voltage function and the blocking
function, as seen in figure
. The delay of the blocking function must be set less than
the time delay of under voltage function.
Section 8
1MRK505222-UUS C
Voltage protection
498
Technical reference manual
Summary of Contents for Relion 670 series
Page 1: ...Relion 670 series Line differential protection RED670 ANSI Technical reference manual...
Page 2: ......
Page 40: ...34...
Page 50: ...44...
Page 60: ...54...
Page 126: ...120...
Page 384: ...378...
Page 496: ...490...
Page 556: ...550...
Page 602: ...596...
Page 620: ...614...
Page 794: ...788...
Page 864: ...858...
Page 988: ...982...
Page 998: ...992...
Page 1084: ...1078...
Page 1164: ...1158...
Page 1168: ...1162...
Page 1220: ...1214...
Page 1230: ...1224...
Page 1231: ...1225...