voltage is lower. If the frequency remains below the set value for a time period
corresponding to the chosen time delay, the corresponding trip signal is issued. To
avoid an unwanted trip due to uncertain frequency measurement at low voltage
magnitude, a voltage controlled blocking of the function is available, that is, if the
voltage is lower than the set blocking voltage
IntBlockLevel
the function is blocked and
no PICKUP or TRIP signal is issued.
9.1.2.1
Measurement principle
The fundamental frequency of the measured input voltage is measured continuously,
and compared with the set value,
PUFrequency
. The frequency function is dependent
on the voltage magnitude. If the voltage magnitude decreases the setting
IntBlockLevel
,
SAPTUF (81) gets blocked, and the output BLKDMAGN is issued. All voltage
settings are made in percent of the setting
VBase
, which should be set as a phase-phase
voltage in kV.
To avoid oscillations of the output PICKUP signal, a hysteresis has been included.
9.1.2.2
Time delay
The time delay for underfrequency protection SAPTUF (81) can be either a settable
definite time delay or a voltage magnitude dependent time delay, where the time delay
depends on the voltage level; a high voltage level gives a longer time delay and a low
voltage level causes a short time delay. For the definite time delay, the setting
TimeDlyOperate
sets the time delay.
For the voltage dependent time delay the measured voltage level and the settings
VNom
,
VMin
,
Exponent
,
t_MaxTripDelay
and
t_MinTripDelay
set the time delay according to
figure
. The setting
TimerOperation
is used to decide what type
of time delay to apply.
Trip signal issuing requires that the underfrequency condition continues for at least the
user set time delay
TimeDlyOperate
. If the PICKUP condition, with respect to the
measured frequency ceases during this user set delay time, and is not fulfilled again
within a user defined reset time,
TimeDlyReset
, the PICKUP output is reset, after that
the defined reset time has elapsed. Here it should be noted that after leaving the
hysteresis area, the PICKUP condition must be fulfilled again and it is not sufficient
for the signal to only return back to the hysteresis area.
On the output of SAPTUF (81) a 100ms pulse is issued, after a time delay
corresponding to the setting of
TimeDlyRestore
, when the measured frequency returns
to the level corresponding to the setting
RestoreFreq
.
Section 9
1MRK505222-UUS C
Frequency protection
552
Technical reference manual
Summary of Contents for Relion 670 series
Page 1: ...Relion 670 series Line differential protection RED670 ANSI Technical reference manual...
Page 2: ......
Page 40: ...34...
Page 50: ...44...
Page 60: ...54...
Page 126: ...120...
Page 384: ...378...
Page 496: ...490...
Page 556: ...550...
Page 602: ...596...
Page 620: ...614...
Page 794: ...788...
Page 864: ...858...
Page 988: ...982...
Page 998: ...992...
Page 1084: ...1078...
Page 1164: ...1158...
Page 1168: ...1162...
Page 1220: ...1214...
Page 1230: ...1224...
Page 1231: ...1225...