12.2.6
Technical data
Table 324:
SMBRREC (79) technical data
Function
Range or value
Accuracy
Number of autoreclosing shots
1 - 5
-
Autoreclosing open time:
shot 1 - t1 1Ph
shot 1 - t1 2Ph
shot 1 - t1 3PhHS
shot 1 - t1 3PhDld
(0.000-60.000) s
± 0.5% ± 10 ms
shot 2 - t2
shot 3 - t3
shot 4 - t4
shot 5 - t5
(0.00-6000.00) s
Extended autorecloser open time
(0.000-60.000) s
Autorecloser maximum wait time for sync
(0.00-6000.00) s
Maximum trip pulse duration
(0.000-60.000) s
Inhibit reset time
(0.000-60.000) s
Reset time
(0.00-6000.00) s
Minimum time CB must be closed before AR
becomes ready for autoreclosing cycle
(0.00-6000.00) s
Circuit breaker closing pulse length
(0.000-60.000) s
CB check time before unsuccessful
(0.00-6000.00) s
Wait for master release
(0.00-6000.00) s
Wait time after close command before proceeding
to next shot
(0.000-60.000) s
12.3
Apparatus control APC
12.3.1
Introduction
The apparatus control functions are used for control and supervision of circuit
breakers, disconnectors and grounding switches within a bay. Permission to operate is
given after evaluation of conditions from other functions such as interlocking,
synchronism check, operator place selection and external or internal blockings.
In normal security, the command is processed and the resulting position is not
supervised. However with enhanced security, the command is processed and the
resulting position is supervised.
Section 12
1MRK505222-UUS C
Control
652
Technical reference manual
Summary of Contents for Relion 670 series
Page 1: ...Relion 670 series Line differential protection RED670 ANSI Technical reference manual...
Page 2: ......
Page 40: ...34...
Page 50: ...44...
Page 60: ...54...
Page 126: ...120...
Page 384: ...378...
Page 496: ...490...
Page 556: ...550...
Page 602: ...596...
Page 620: ...614...
Page 794: ...788...
Page 864: ...858...
Page 988: ...982...
Page 998: ...992...
Page 1084: ...1078...
Page 1164: ...1158...
Page 1168: ...1162...
Page 1220: ...1214...
Page 1230: ...1224...
Page 1231: ...1225...