Table 1:
Function of selections
Selection
Function
S1
File version of setfile:
•
preliminary versions → for example, 0.10, 0.20 ….
•
commissioned versions → for example, 1.00, 2.00 ….
S2
Revision index of setfile:
•
setting changes on site → A, B,.. up to AY, AZ
5.1.1
System data
GUID-4B93572D-E320-4624-BA37-213534C3B52C v1
Specified data
General system information as well as the type of installation is entered on the left hand side
under Specified data.
Licensed data
On the right hand side, the Licensed components (that is, the licensed protection functions) have
to be entered. This selection of licensed function in the setfile has to match with the licensed
function scope of the ordered Bay Units.
5.1.2
File version management system
GUID-B1FCC2E2-F1BB-40D8-A43E-12F90D079A97 v2
The HMI500 tool contains a file version management system which is active under the
Configurator mode only. The file version (see
, selection S1) will be added to the file name
by default. During configuration/testing/commissioning phase, it is recommended to use
preliminary versions such as 0.1, 0.2. The commissioned file version shall be incremented to 1.0.
For major configuration updates, the first digit shall be incremented (for eample, 1.0 to 2.0). For
minor updates the second digit of the file version index has to be incremented (for example, 1.0 to
1.1).
Definition major update
•
New configuration of primary system (which was not pre-configured)
•
Additional Bay Unit (which was not pre-configured)
•
Additional functionality as BFP, UMZ etc.
•
Setfile migration (software upgrade)
Definition minor update
•
New binary I/O configuration (implemented by the setfile engineer)
•
New protection settings (implemented by the setfile engineer)
The file revision index A, B, up to AY, AZ (see
, selection S2) shall be used for setting
changes on site (not for configuration changes done under the Configurator mode). This index
shall be changed in the HMI500 Operator mode.
Section 5
1MRK 511 452-UUS Rev. A
Configuration
18
Distributed busbar protection REB500
Engineering manual
© 2020 Hitachi Power Grids. All rights reserved