After starting the File verification tool, the content, structure and completeness of the REB500
setfile is checked.
This test routine shall be started after the setfile configuration has been completed. Once the test
run is finished, the HMI500 menu shows the test result. For a successful test run, the system
provides the information Number of errors: 0, Number of warnings: 0.
IEC18000585-IEC18000585-1-en.vsdx
IEC18000585 V1 EN-US
Figure 17: File verification — no errors
If the test procedure locates a setfile inconsistency, then an error level and a short description of
the problem is given:
•
Error level 1 (minor error)
Such errors are caused by incomplete settings and configurations in the setfile (for example,
CU device creator not started). An error level1 is mostly accompanied by errors level 2 and 3.
These error messages (side effect) should be cleared, after the errors level 1 are fixed. The
repetition of the file verification shall prove the setfile again.
•
Error level > 1 (major error)
If errors level >1 should remain after the errors level 1 are fixed, the setfile has an important
inconsistency, which cannot be solved by the user (engineer) of the HMI500 Tool, please
contact your HMI500 supplier for clarification.
It is mandatory, to start the test run after the setfile configuration has been
finished.
7.2
Reports
GUID-2842D78B-C0D7-408A-A262-F618DB28EAFB v1
For detailed information about setting and configuration, see
REB500 Operation Manual, section
Reports.
1MRK 511 452-UUS Rev. A
Section 7
Tools
Distributed busbar protection REB500
37
Engineering manual
© 2020 Hitachi Power Grids. All rights reserved