8.4
Configuration models (3)
GUID-0898CF32-0B9D-4519-9DB1-9E05EF2B64C9 v3
FUNCT.
I/O
Objects
FUNCT.
I/O
FUNCT.
I/O
Objects
Objects
Bay Unit 2
Bay Unit 3
Bay Unit 1
FUNCT.
I/O
Objects
FUNCT.
I/O
FUNCT.
I/O
Objects
Objects
Bay Unit 2
Bay Unit 3
Bay Unit 1
Bay Model containing more than one Bay Figure AND more than one Bay Unit
Model
This type of Bay Model, is called Multiple Bay Model (MBM).
➢
For example, a Multiple Bay Model for a complete 1 ½ - breaker bay
Multiple Bay Models are allowed, if following limitations are not exceeded:
•
Number of CB objects number of bay units
•
Number of CT objects number of bay units
•
Number of VT objects number of bay units
•
From the Bay Model side, the number of disconnectors is not limited, if the number of
binary inputs is sufficient.
ANSI18000618 V1 EN-US
1MRK 511 452-UUS Rev. A
Section 8
Annex A | Configurator mode - Definitions
Distributed busbar protection REB500
47
Engineering manual
© 2020 Hitachi Power Grids. All rights reserved