Interlock, transformer bay AB_TRAFO
Main menu/Test/Function status/Control/Apparatus control/
InterlTransformerBay/AB_TRAFO:x
Shows available instances of the function with several measurements per instance.
The measurements indicate which breakers and disconnectors are permitted to open
and/or close, the status of the disconnect devices and switch status validity. For
example, the measurement named VPQB2TR indicates with output value 1 that the
switch status of disconnector QB2 is valid.
Bay reserve QCRSV
Main menu/Test/Function status/Control/Apparatus control/
BayReserve(CRSV)/QCRSV:x
Displays available instances of the function QCRSV with several measurements
per instance. Apart from the measurement for exchange signals between different
BayRes blocks the output values are all boolean and indicate the status of processes
and devices.
Bay control QCBAY
Main menu/Test/Function status/Control/ApparatusControl/BayControl/
QCBAY:x
Displays available instances of the function QCBAY with three measurements per
instance. The operator place allocation (PSTO) measurement has an integer as
output data, whereas the Update of position is blocked (UPD_BLKD) and Function
is blocked for commands (CMD_BLKD) have boolean output data.
11.6.7.2
Autorecloser SMBRREC
Main menu/Test/Function status/Control/AutoRecloser(RREC,79)/
SMBRREC:x
Displays an application dependent number of instances of SMBRREC with a
number of measurements per instance that include data on the progress and state of
the reclosing function. There is data indicating whether the Ar is in a blocked state,
data indicating what kind of reclosing is in progress and data indicating the number
of reclosing shots. Auto reclosing status is also indicated by 1=ready, 2=In
progress, 3=Successful.
11.6.7.3
Commands
In the commands menu it is possible to view three sets of values. These are found
under the submenus menucascade/uicontrol.
Automation bits, command function for DNP3.0 AutomationBits
Main menu/Test/Function status/Control/Commands/Automation Bits/
AUTOBITS:x
Section 11
1MRK505209-UEN E
Test the IED
78
Operator's manual