PSCLOSED
signal must become active a certain time (>150 ms) before current starts
flowing for example, through arcing. Otherwise this current will not be taken into
account in the busbar protection and this can result in a maloperation. Therefore, good
timing of two auxiliary contacts is definitely required.
The time during which the
POSOPEN
and
POSCLOSED
signals disagree (that is, both
binary inputs are active or both are inactive) is monitored by the isolator supervision
function for both of the above two schemes. The maximum time allowed before an
alarm is given can be set according to the disconnector timing.
Table
and the following two figures summarize the properties of these two schemes.
Table 13:
Treatment of primary object auxiliary contact status within BBP in REB670
Primary equipment
Status in busbar protection
Alarm facility
Normally
Open
auxiliary
contact status
(“closed” or
“a” contact)
Normally
Closed
auxiliary
contact status
(“open” or “b”
contact)
when
“Scheme 1
RADSS”
is selected
when
“Scheme 2
INX”
is selected
Alarm after
settable time
delay
Information visible on
local HMI
open
open
closed
Last
position
saved
yes
intermediate_00
open
closed
open
open
no
open
closed
open
closed
closed
no
closed
closed
closed
closed
closed
yes
badState_11
BBP
input „closed“
input „open“
N.O.
N.C.
1
0
1
0
1
0
closed
open
arcing possible
current
assignment
1)
1)
1) disconnector supervision running
en06000084.vsd
IEC06000084 V1 EN-US
Figure 43:
Scheme1_RADSS
Section 6
1MRK 505 370-UUS A
Differential protection
118
Busbar protection REB670 2.2 ANSI
Application manual
Summary of Contents for RELION REB670
Page 1: ...RELION 670 SERIES Busbar protection REB670 Version 2 2 ANSI Application manual ...
Page 2: ......
Page 24: ...18 ...
Page 40: ...34 ...
Page 72: ...66 ...
Page 102: ...96 ...
Page 266: ...260 ...
Page 272: ...266 ...
Page 290: ...284 ...
Page 432: ...426 ...
Page 542: ...536 ...
Page 552: ...546 ...
Page 553: ...547 ...