related disconnectors. In addition, in two-zone busbar differential protections, a setting
parameter is also introduced to determine, together with the binary inputs, how the bay
CT current shall be connected to the differential zones.
The philosophy is to allow every CT input to be individually controlled by a setting
parameter. This parameter called
ZoneSel
can be individually configured for every CT
input. This parameter, for every bay, can be set to only one of the following five
alternatives:
1.
FIXEDtoZA
2.
FIXEDtoZB
3.
FIXEDtoZA&-ZB
4.
CtrlIncludes
5.
CtrlExcludes
If for a particular CT input setting parameter
ZoneSel
is set to
FIXEDtoZA
, then this
CT input will be only included to the differential zone A. This setting is typically used
for simple single zone application such as: single busbar staions, breaker-and-a-half
stations or double breaker stations.
If for a particular CT input setting parameter
ZoneSel
is set to
FIXEDtoZB
, then this
CT input will be only included to the differential zone B. This setting is typically used
for applications such as: breaker-and-a-half stations or double breaker stations.
If for a particular CT input setting parameter
ZoneSel
is set to
FIXEDtoZA&-ZB
, then
this CT input will be included to the differential zone A, but its inverted current value
will be as well included to the differential zone B. This setting is typically used for bus
coupler or bus section bays when only one current transformer is available see Figure
If for a particular CT input setting parameter
ZoneSel
is set to
Ctrl_Includes
, then this
CT input will be:
•
included to the differential zone A when input signal CTRLZA on corresponding
bay block is given logical value one and it will be excluded from the differential
zone A when input signal CTRLZA on corresponding bay block is given logical
value zero.
•
included to the differential zone B when input signal CTRLZB on corresponding
bay block is given logical value one and it will be excluded from the differential
zone B when input signal CTRLZB on corresponding bay block is given logical
value zero.
This setting is typically used for feeder bays in double busbar stations in order to form
proper busbar disconnector replica. It is especially suitable both when normally open
1MRK 505 370-UUS A
Section 6
Differential protection
Busbar protection REB670 2.2 ANSI
121
Application manual
Summary of Contents for RELION REB670
Page 1: ...RELION 670 SERIES Busbar protection REB670 Version 2 2 ANSI Application manual ...
Page 2: ......
Page 24: ...18 ...
Page 40: ...34 ...
Page 72: ...66 ...
Page 102: ...96 ...
Page 266: ...260 ...
Page 272: ...266 ...
Page 290: ...284 ...
Page 432: ...426 ...
Page 542: ...536 ...
Page 552: ...546 ...
Page 553: ...547 ...