Only one measuring circuit is utilized for all fault types (that is, no redundancy for
multi-phase faults)
•
Primary fault sensitivity varies depending on the type of fault and involved
phase(s), see Table
•
The load currents in the healthy phases might produce the stabilizing current when
an internal single phase to ground fault occurs. However, there is no problem for
solidly gounded systems with high ground-fault currents
•
No indication of faulty phase(s) in case of an internal fault
•
Not possible to fully utilize Open CT detection feature
6.1.6.2
Auxiliary summation CTs
M12136-4 v4
Auxiliary Summation Current Transformer (that is, ASCT in further text) of the type
SLCE 8 is used with the summation principle of the IED. The principle drawing of one
such ASCT is shown in Figure
Auxiliary Summation CT
type SLCE 8; X/1A
N4
S1
S2
en03000118_ansi.vsd
P1
N1
P2
P3
N2
P4
P5
N3
P6
ANSI03000118 V1 EN-US
Figure 84:
Principle ASCT drawing
The ASCT has three primary windings and one secondary winding. In further text, turn
numbers of these windings will be marked with N1, N2, N3 & N4, respectively (see
Figure
There are three types of ASCT for REB670:
Section 6
1MRK 505 370-UUS A
Differential protection
166
Busbar protection REB670 2.2 ANSI
Application manual
Summary of Contents for RELION REB670
Page 1: ...RELION 670 SERIES Busbar protection REB670 Version 2 2 ANSI Application manual ...
Page 2: ......
Page 24: ...18 ...
Page 40: ...34 ...
Page 72: ...66 ...
Page 102: ...96 ...
Page 266: ...260 ...
Page 272: ...266 ...
Page 290: ...284 ...
Page 432: ...426 ...
Page 542: ...536 ...
Page 552: ...546 ...
Page 553: ...547 ...