40
100
40
40
220
t
ms
ms
ms
ms
ms
D ³
+
+
+
=
EQUATION1266 V1 EN-US
(Equation 29)
where it is considered that:
the operate time of overcurrent protection B1 is 40 ms
the breaker open time
is 100 ms
the resetting time of protection A1
is 40 ms and
the additional margin
is 40 ms
7.2
Four step single phase overcurrent protection
PH4SPTOC (51)
SEMOD127812-1 v2
7.2.1
Identification
SEMOD127810-2 v2
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Four step single phase overcurrent
protection
PH4SPTOC
4
4
alt
I>
OC V1 EN-US
51
7.2.2
Application
SEMOD127937-4 v2
The Four step single phase overcurrent protection(PH4SPTOC, 51) function is used in
several applications in the power system. Some applications are:
•
Short circuit protection of feeders in distribution and subtransmission systems.
Normally these feeders have radial structure.
•
Back-up short circuit protection of transmission lines.
•
Back-up short circuit protection of power transformers
•
Short circuit protection of different kinds of equipment connected to the power
system such as; shunt capacitor banks, shunt reactors, motors and others.
•
Back-up short circuit protection of power generators.
The single phase overcurrent protection is used in IEDs having only input from one
phase, for example busbar protection for large busbars (with many bays).
1MRK 505 370-UUS A
Section 7
Current protection
Busbar protection REB670 2.2 ANSI
187
Application manual
Summary of Contents for RELION REB670
Page 1: ...RELION 670 SERIES Busbar protection REB670 Version 2 2 ANSI Application manual ...
Page 2: ......
Page 24: ...18 ...
Page 40: ...34 ...
Page 72: ...66 ...
Page 102: ...96 ...
Page 266: ...260 ...
Page 272: ...266 ...
Page 290: ...284 ...
Page 432: ...426 ...
Page 542: ...536 ...
Page 552: ...546 ...
Page 553: ...547 ...