SeqTypeUPol
: This is used to select the type of voltage polarising quantity i.e. Zero seq
and Neg seq for direction detection.
SeqTypeIPol
: This is used to select the type of current polarising quantity i.e. Zero seq
and Neg seq for direction detection.
SeqTypeIDir
: This is used to select the type of operating current quantity i.e. Zero seq
and Neg seq for direction detection.
7.3.2.1
Common settings for all steps
M15282-81 v10
AngleRCA
: Relay characteristic angle given in degree. This angle is defined as shown
. The angle is defined positive when the residual current lags the reference
voltage (Vpol = 3V
0
or V
2
)
V pol = 3V
0
or V
2
RCA
Operation
IDirPU
en 05000135-4- ansi.vsd
ANSI05000135 V3 EN-US
Figure 95:
Relay characteristic angle given in degree
In a normal transmission network a normal value of RCA is about 65°. The setting
range is -180° to +180°.
polMethod
: Defines if the directional polarization is from
Section 7
1MRK 505 370-UUS A
Current protection
198
Busbar protection REB670 2.2 ANSI
Application manual
Summary of Contents for RELION REB670
Page 1: ...RELION 670 SERIES Busbar protection REB670 Version 2 2 ANSI Application manual ...
Page 2: ......
Page 24: ...18 ...
Page 40: ...34 ...
Page 72: ...66 ...
Page 102: ...96 ...
Page 266: ...260 ...
Page 272: ...266 ...
Page 290: ...284 ...
Page 432: ...426 ...
Page 542: ...536 ...
Page 552: ...546 ...
Page 553: ...547 ...