kx
: Time multiplier for the dependent (inverse) characteristic for step
x
.
IMinx
: Minimum pickup current for step
x
in % of
IB
. Set
IMinx
below
Pickupx
for
every step to achieve ANSI reset characteristic according to standard. If
IMinx
is set
above for any step, signal will reset at current equals to zero.
txMin
: Minimum operating time for inverse time characteristics. At high currents, the
inverse time characteristic might give a very short operation time. By setting this
parameter, the operation time of the step can never be shorter than the setting.
ANSI10000058-1-en.vsdx
Trip time
Pickup current
tx
txMin
ANSI10000058 V1 EN-US
Figure 97:
Minimum pickup current and trip time for inverse time characteristics
In order to fully comply with the curves definition, the setting parameter
txMin
shall be
set to the value which is equal to the operate time of the selected IEC inverse curve for
measured current of twenty times the set current pickup value. Note that the operate
time value is dependent on the selected setting value for time multiplier
kx
.
INxMult
: Multiplier for scaling of the current setting value. If a binary input signal
(MULTPUx) is activated, the current operation level is increased by this setting
constant.
ResetTypeCrvx
: The reset of the delay timer can be made in different ways. The
possibilities are described in the technical reference manual.
tResetx
: Constant reset time delay in s for step x.
1MRK 505 370-UUS A
Section 7
Current protection
Busbar protection REB670 2.2 ANSI
203
Application manual
Summary of Contents for RELION REB670
Page 1: ...RELION 670 SERIES Busbar protection REB670 Version 2 2 ANSI Application manual ...
Page 2: ......
Page 24: ...18 ...
Page 40: ...34 ...
Page 72: ...66 ...
Page 102: ...96 ...
Page 266: ...260 ...
Page 272: ...266 ...
Page 290: ...284 ...
Page 432: ...426 ...
Page 542: ...536 ...
Page 552: ...546 ...
Page 553: ...547 ...