Tau1Low
: Multiplication factor to adjust the time constant
Tau1
if the current is lower
than the set value
ILowTau1
.
ILowTau1
is set in % of
IBase1
.
Tau2High
: Multiplication factor to adjust the time constant
Tau2
if the current is higher
than the set value
IHighTau2
.
IHighTau2
is set in % of
IBase2
.
Tau2Low
: Multiplication factor to adjust the time constant
Tau2
if the current is lower
than the set value
ILowTau2
.
ILowTau2
is set in % of
IBase2
.
The possibility to change time constant with the current value as the base can be useful
in different applications. Below some examples are given:
•
In case a total interruption (low current) of the protected transformer all cooling
possibilities will be inactive. This can result in a changed value of the time
constant.
•
If other components (motors) are included in the thermal protection, there is a risk
of overheating of that equipment in case of very high current. The thermal time
constant is often smaller for a motor than for the transformer.
ITrip:
The steady state current that the transformer can withstand. The setting is given
in % of
IBase1
or
IBase2
.
Alarm1
: Heat content level for activation of the signal ALARM1. ALARM1 is set in %
of the trip heat content level.
Alarm2
: Heat content level for activation of the output signal ALARM2. ALARM2 is
set in % of the trip heat content level.
LockoutReset
: Lockout release level of heat content to release the lockout signal. When
the thermal overload protection trips a lock-out signal is activated. This signal is
intended to block switching on of the protected circuit transformer as long as the
transformer temperature is high. The signal is released when the estimated heat content
is below the set value. This temperature value should be chosen below the alarm
temperature.
LockoutReset
is set in % of the trip heat content level.
ThetaInit
: Heat content before activation of the function. This setting can be set a little
below the alarm level. If the transformer is loaded before the activation of the
protection function, its temperature can be higher than the ambient temperature. The
start point given in the setting will prevent risk of no trip at overtemperature during the
first moments after activation.
ThetaInit:
is set in % of the trip heat content level.
Warning
: If the calculated time to trip factor is below the setting
Warning
a warning
signal is activated. The setting is given in minutes.
Section 7
1MRK 505 370-UUS A
Current protection
214
Busbar protection REB670 2.2 ANSI
Application manual
Summary of Contents for RELION REB670
Page 1: ...RELION 670 SERIES Busbar protection REB670 Version 2 2 ANSI Application manual ...
Page 2: ......
Page 24: ...18 ...
Page 40: ...34 ...
Page 72: ...66 ...
Page 102: ...96 ...
Page 266: ...260 ...
Page 272: ...266 ...
Page 290: ...284 ...
Page 432: ...426 ...
Page 542: ...536 ...
Page 552: ...546 ...
Page 553: ...547 ...