applications
1 out of 3
is sufficient. For
Contact
operation means back-up trip is done
when circuit breaker is closed (breaker position is used).
Pickup_PH
: Current level for detection of breaker failure, set in % of
IBase
. This
parameter should be set so that faults with small fault current can be detected. The
setting can be chosen in accordance with the most sensitive protection function to start
the breaker failure protection. Typical setting is 10% of
IBase
.
Pickup_BlkCont
: If any contact based detection of breaker failure is used, this function
can be blocked if any phase current is larger than this setting level. If the
FunctionMode
is set
Current/Contact
breaker failure for high current faults are safely
detected by the current measurement function. To increase security the contact based
function should be disabled for high currents. The setting can be given within the range
5 – 200% of
IBase
.
Pickup_N
: Residual current level for detection of breaker failure set in % of
IBase
. In
high impedance grounded systems the residual current at phase- to-ground faults are
normally much smaller than the short circuit currents. In order to detect breaker failure
at single-phase-ground faults in these systems it is necessary to measure the residual
current separately. Also in effectively grounded systems the setting of the ground-fault
current protection can be chosen to relatively low current level. The
BuTripMode
is set
1 out of 4
. The current setting should be chosen in accordance to the setting of the
sensitive ground-fault protection. The setting can be given within the range 2 – 200 %
of
IBase
.
t1
: Time delay of the re-trip. The setting can be given within the range 0 – 60s in steps
of 0.001 s. Typical setting is 0 – 50ms.
t2
: Time delay of the back-up trip. The choice of this setting is made as short as
possible at the same time as unwanted operation must be avoided. Typical setting is 90
– 200ms (also dependent of re-trip timer).
The minimum time delay for the re-trip can be estimated as:
_
2
1
³ +
+
+
cbopen
BFP reset
margin
t
t
t
t
t
EQUATION1430 V1 EN-US
(Equation 39)
where:
t
cbopen
is the maximum opening time for the circuit breaker
t
BFP_reset
is the maximum time for breaker failure protection to detect correct breaker function (the
current criteria reset)
t
margin
is a safety margin
1MRK 505 370-UUS A
Section 7
Current protection
Busbar protection REB670 2.2 ANSI
217
Application manual
Summary of Contents for RELION REB670
Page 1: ...RELION 670 SERIES Busbar protection REB670 Version 2 2 ANSI Application manual ...
Page 2: ......
Page 24: ...18 ...
Page 40: ...34 ...
Page 72: ...66 ...
Page 102: ...96 ...
Page 266: ...260 ...
Page 272: ...266 ...
Page 290: ...284 ...
Page 432: ...426 ...
Page 542: ...536 ...
Page 552: ...546 ...
Page 553: ...547 ...