tPulse
: Trip pulse duration. This setting must be larger than the critical impulse time of
circuit breakers to be tripped from the breaker failure protection. Typical setting is 200
ms.
7.7
Breaker failure protection, single phase version
CCSRBRF (50BF)
SEMOD127864-1 v2
7.7.1
Identification
SEMOD127866-2 v2
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Breaker failure protection, single phase
version
CCSRBRF
I>BF
SYMBOL-II V1 EN-US
50BF
7.7.2
Application
SEMOD127974-4 v2
In the design of the fault clearance system the N-1 criterion is often used. This means
that a fault shall be cleared even if any component in the fault clearance system is
faulty. One necessary component in the fault clearance system is the circuit breaker. It
is from practical and economical reason not feasible to duplicate the circuit breaker for
the protected component. Instead a breaker failure protection is used.
Breaker failure protection, single phase version (CCSRBRF,50BF) function will issue
a back-up trip command to adjacent circuit breakers in case of failure to trip of the
“normal” circuit breaker for the protected component. The detection of failure to break
the current through the breaker is made by means of current measurement or as
detection of remaining trip signal (unconditional).
CCSRBRF (50BF) function can also give a re-trip. This means that a second trip signal
is sent to the protected circuit breaker. The re-trip function can be used to increase the
probability of operation of the breaker, or it can be used to avoid back-up trip of many
breakers in case of mistakes during relay maintenance and test.
7.7.3
Setting guidelines
SEMOD127980-4 v5
The parameters for Breaker failure protection, single phase version (CCSRBRF,50BF)
are set via the local HMI or PCM600.
The following settings can be done for the breaker failure protection.
1MRK 505 370-UUS A
Section 7
Current protection
Busbar protection REB670 2.2 ANSI
219
Application manual
Summary of Contents for RELION REB670
Page 1: ...RELION 670 SERIES Busbar protection REB670 Version 2 2 ANSI Application manual ...
Page 2: ......
Page 24: ...18 ...
Page 40: ...34 ...
Page 72: ...66 ...
Page 102: ...96 ...
Page 266: ...260 ...
Page 272: ...266 ...
Page 290: ...284 ...
Page 432: ...426 ...
Page 542: ...536 ...
Page 552: ...546 ...
Page 553: ...547 ...