Operate
Angle1(2) = 0
°
Power1(2)
P
Q
en06000556.vsd
IEC06000556 V1 EN-US
Figure 104:
For low forward power the set angle should be 0° in the underpower
function
TripDelay1(2)
is set in seconds to give the time delay for trip of the stage after pick up.
Hysteresis1(2)
is given in p.u. of generator rated power according to equation
.
N
S
3 VBase IBase
=
×
×
EQUATION2047 V1 EN-US
(Equation 52)
The drop out power will be
Power1(2) + Hysteresis1(2)
.
The possibility to have low pass filtering of the measured power can be made as shown
in the formula:
S
TD S
TD
S
Old
Calculated
=
⋅
+
−
(
)
⋅
1
EQUATION1893-ANSI V1 EN-US
(Equation 53)
Where
S
is a new measured value to be used for the protection function
S
old
is the measured value given from the function in previous execution cycle
S
Calculated
is the new calculated value in the present execution cycle
TD
is settable parameter
1MRK 505 370-UUS A
Section 7
Current protection
Busbar protection REB670 2.2 ANSI
227
Application manual