phase-to-phase voltages VAB, VBC and VCA. This information about actual VT
connection is entered as a setting parameter for the pre-processing block, which will
then take automatically care about it.
10.1.2.2
Base quantities for CVGAPC function
SEMOD53443-112 v3
The parameter settings for the base quantities, which represent the base (100%) for
pickup levels of all measuring stages shall be entered as setting parameters for every
CVGAPC function.
Base current shall be entered as:
1. rated phase current of the protected object in primary amperes, when the measured
Current Quantity is selected from 1 to 9, as shown in table
2. rated phase current of the protected object in primary amperes multiplied by √3
(1.732 x Iphase), when the measured Current Quantity is selected from 10 to 15, as
shown in table
Base voltage shall be entered as:
1. rated phase-to-ground voltage of the protected object in primary kV, when the
measured Voltage Quantity is selected from 1 to 9, as shown in table
2. rated phase-to-phase voltage of the protected object in primary kV, when the
measured Voltage Quantity is selected from 10 to 15, as shown in table
.
10.1.2.3
Application possibilities
SEMOD53443-136 v2
Due to its flexibility the general current and voltage protection (CVGAPC) function
can be used, with appropriate settings and configuration in many different applications.
Some of possible examples are given below:
1. Transformer and line applications:
•
Underimpedance protection (circular, non-directional characteristic) (21)
•
Underimpedance protection (circular mho characteristic) (21)
•
Voltage Controlled/Restrained Overcurrent protection (51C, 51V)
•
Phase or Negative/Positive/Zero Sequence (Non-Directional or Directional)
Overcurrent protection (50, 51, 46, 67, 67N, 67Q)
•
Phase or phase-to-phase or Negative/Positive/Zero Sequence over/under
voltage protection (27, 59, 47)
•
Special thermal overload protection (49)
•
Open Phase protection
•
Unbalance protection
2. Generator protection
1MRK 505 370-UUS A
Section 10
Multipurpose protection
Busbar protection REB670 2.2 ANSI
271
Application manual
Summary of Contents for RELION REB670
Page 1: ...RELION 670 SERIES Busbar protection REB670 Version 2 2 ANSI Application manual ...
Page 2: ......
Page 24: ...18 ...
Page 40: ...34 ...
Page 72: ...66 ...
Page 102: ...96 ...
Page 266: ...260 ...
Page 272: ...266 ...
Page 290: ...284 ...
Page 432: ...426 ...
Page 542: ...536 ...
Page 552: ...546 ...
Page 553: ...547 ...