EQUATION1740-ANSI V1 EN-US
(Equation 74)
where:
t
op
is the operating time in seconds of the negative sequence overcurrent IED
TD
is the generator capability constant in seconds
I
NS
is the measured negative sequence current
I
r
is the generator rated current
By defining parameter x equal to maximum continuous negative sequence rating of the
generator in accordance with the following formula
7%
0.07
=
=
x
pu
EQUATION1756-ANSI V1 EN-US
(Equation 75)
Equation
can be re-written in the following way without changing the value for the
operate time of the negative sequence inverse overcurrent IED:
op
2
NS
r
2
TD
t
I
x I
1
x
×
=
×
æ
ö
ç
÷
è
ø
EQUATION1741-ANSI V1 EN-US
(Equation 76)
In order to achieve such protection functionality with one CVGAPC functions the
following must be done:
1. Connect three-phase generator currents to one CVGAPC instance (for example,
GF01)
2. Set parameter
CurrentInput
to value
NegSeq
3. Set base current value to the rated generator current in primary amperes
4. Enable one overcurrent step (for example, OC1)
5. Select parameter
CurveType_OC1
to value
Programmable
Section 10
1MRK 505 370-UUS A
Multipurpose protection
276
Busbar protection REB670 2.2 ANSI
Application manual
Summary of Contents for RELION REB670
Page 1: ...RELION 670 SERIES Busbar protection REB670 Version 2 2 ANSI Application manual ...
Page 2: ......
Page 24: ...18 ...
Page 40: ...34 ...
Page 72: ...66 ...
Page 102: ...96 ...
Page 266: ...260 ...
Page 272: ...266 ...
Page 290: ...284 ...
Page 432: ...426 ...
Page 542: ...536 ...
Page 552: ...546 ...
Page 553: ...547 ...