high value of voltage 3V
2
without the presence of the negative-sequence current 3I
2
is
a condition that is related to a fuse failure event.
The zero sequence detection algorithm, based on the zero sequence measuring
quantities is recommended for use in directly or low impedance grounded networks: a
high value of voltage 3V
0
without the presence of the residual current 3I
0
is a condition
that is related to a fuse failure event. In cases where the line can have a weak-infeed of
zero sequence current this function shall be avoided.
A criterion based on delta current and delta voltage measurements can be added to the
fuse failure supervision function in order to detect a three phase fuse failure. This is
beneficial for example during three phase transformer switching.
11.1.3
Setting guidelines
IP15000-1 v1
11.1.3.1
General
M13683-3 v5
The negative and zero sequence voltages and currents always exist due to different
non-symmetries in the primary system and differences in the current and voltage
instrument transformers. The minimum value for the operation of the current and
voltage measuring elements must always be set with a safety margin of 10 to 20%,
depending on the system operating conditions.
Pay special attention to the dissymmetry of the measuring quantities when the function
is used on long untransposed lines, on multicircuit lines and so on.
The settings of negative sequence, zero sequence and delta algorithm are in percent of
the base voltage and base current for the function. Common base IED values for
primary current (
IBase
), primary voltage (
VBase
) and primary power (
SBase
) are set in
Global Base Values
GBASVAL
. The setting
GlobalBaseSel
is used to select a particular
GBASVAL
and used its base values.
11.1.3.2
Setting of common parameters
M13683-9 v9
Set the operation mode selector
Operation
to
Enabled
to release the fuse failure
function.
The voltage threshold
VPPU
is used to identify low voltage condition in the system.
Set
VPPU
below the minimum operating voltage that might occur during emergency
conditions. We propose a setting of approximately 70% of
VBase
.
The drop off time of 200 ms for dead phase detection makes it recommended to always
set
SealIn
to
Enabled
since this will secure a fuse failure indication at persistent fuse
fail when closing the local breaker when the line is already energized from the other
end. When the remote breaker closes the voltage will return except in the phase that
Section 11
1MRK 505 370-UUS A
Secondary system supervision
286
Busbar protection REB670 2.2 ANSI
Application manual
Summary of Contents for RELION REB670
Page 1: ...RELION 670 SERIES Busbar protection REB670 Version 2 2 ANSI Application manual ...
Page 2: ......
Page 24: ...18 ...
Page 40: ...34 ...
Page 72: ...66 ...
Page 102: ...96 ...
Page 266: ...260 ...
Page 272: ...266 ...
Page 290: ...284 ...
Page 432: ...426 ...
Page 542: ...536 ...
Page 552: ...546 ...
Page 553: ...547 ...