PhaseDiffA
setting. Fluctuations occurring at high speed autoreclosing limit
PhaseDiffA
setting.
tSCM
and
tSCA
The purpose of the timer delay settings,
tSCM
and
tSCA
, is to ensure that the
synchrocheck conditions remains constant and that the situation is not due to a
temporary interference. Should the conditions not persist for the specified time, the
delay timer is reset and the procedure is restarted when the conditions are fulfilled
again. Circuit breaker closing is thus not permitted until the synchrocheck situation has
remained constant throughout the set delay setting time. Manual closing is normally
under more stable conditions and a longer operation time delay setting is needed,
where the
tSCM
setting is used. During auto-reclosing, a shorter operation time delay
setting is preferable, where the
tSCA
setting is used. A typical value for
tSCM
can be 1
second and a typical value for
tSCA
can be 0.1 seconds.
Energizingcheck settings
AutoEnerg
and
ManEnerg
Two different settings can be used for automatic and manual closing of the circuit
breaker. The settings for each of them are:
•
Disabled
, the energizing function is disabled.
•
DLLB
, Dead Line Live Bus, the line voltage is below set value of
VDeadLineEnerg
and the bus voltage is above set value of
VLIveBusEnerg
.
•
DBLL
, Dead Bus Live Line, the bus voltage is below set value of
VDeadBusEnerg
and the line voltage is above set value of
VLiveLineEnerg
.
•
Both
, energizing can be done in both directions,
DLLB
or
DBLL
.
ManEnergDBDL
If the parameter is set to
Enabled
, manual closing is also enabled when both line
voltage and bus voltage are below
VDeadLineEnerg
and
VDeadBusEnerg
respectively,
and
ManEnerg
is set to
DLLB
,
DBLL
or
Both
.
VLiveBusEnerg
and
VLiveLineEnerg
The voltage level settings must be chosen in relation to the bus or line network voltage.
The threshold voltages
VLiveBusEnerg
and
VLiveLineEnerg
have to be set lower than
the value at which the network is considered to be energized. A typical value can be
80% of the base voltages.
VDeadBusEnerg
and
VDeadLineEnerg
Section 12
1MRK 505 370-UUS A
Control
312
Busbar protection REB670 2.2 ANSI
Application manual
Summary of Contents for RELION REB670
Page 1: ...RELION 670 SERIES Busbar protection REB670 Version 2 2 ANSI Application manual ...
Page 2: ......
Page 24: ...18 ...
Page 40: ...34 ...
Page 72: ...66 ...
Page 102: ...96 ...
Page 266: ...260 ...
Page 272: ...266 ...
Page 290: ...284 ...
Page 432: ...426 ...
Page 542: ...536 ...
Page 552: ...546 ...
Page 553: ...547 ...