ACTIVE
Indicates that the auto recloser is active, from start until end of reset time.
BLOCKED
Indicates that auto recloser is temporarily or permanently blocked.
CLOSECMD
Connect to a binary output for circuit breaker closing command.
COUNT1P, COUNT2P, COUNT3P1, COUNT3P2, COUNT3P3,
COUNT3P4 and COUNT3P5
Indicates the number of auto reclosing shots made for respective shot.
COUNTAR
Indicates the total number of auto reclosing shots made.
INHIBOUT
If the
INHIBIT
input is activated it is reported on the
INHIBOUT
output.
INPROGR
Indicates that an auto recloser sequence is in progress, from start until circuit breaker
close command.
MODE
When a valid integer is connected to the
MODEINT
input, the selected
ARMode
setting
will be invalid and the
MODEINT
input value will be used instead. The selected mode
is reported as an integer on the
MODE
output. The six possible modes are described in
Table
with their corresponding
MODEINT
integer value.
PERMIT1P
Permit single-pole trip is the inverse of
PREP3P
. It can be connected to a binary output
relay for connection to external protection or trip relays. In case of a total loss of
auxiliary power, the output relay drops and does not allow single-pole trip.
PREP3P
Prepare three-pole trip is usually connected to the trip block to force a coming trip to
be a three-pole one. If the auto recloser cannot make a single-pole or two-pole auto
reclosing, the tripping should be three-pole.
1MRK 505 370-UUS A
Section 12
Control
Busbar protection REB670 2.2 ANSI
331
Application manual
Summary of Contents for RELION REB670
Page 1: ...RELION 670 SERIES Busbar protection REB670 Version 2 2 ANSI Application manual ...
Page 2: ......
Page 24: ...18 ...
Page 40: ...34 ...
Page 72: ...66 ...
Page 102: ...96 ...
Page 266: ...260 ...
Page 272: ...266 ...
Page 290: ...284 ...
Page 432: ...426 ...
Page 542: ...536 ...
Page 552: ...546 ...
Page 553: ...547 ...