IEC16000072 V1 EN-US
Figure 136:
Configuration with XLNPROXY and GOOSEXLNRCV where only the
mandatory data in the IEC 61850 modelling is used
All the information from the XLNPROXY to the SCSWI about command following
status, causes for failed command and selection status is transferred in the output
XPOS. The other outputs may be used by other functions in the same way as the
corresponding outputs of the SXCBR and SXSWI function.
When a command has been issued from the connected SCSWI function, the
XLNPROXY function awaits the response on it from the represented switch through
the inputs POSVAL and OPOK. While waiting for the switch to start moving, it checks
if the switch is blocked for the operation. When the switch has started moving and no
blocking condition has been detected, XLNPROXY issues a response to the SCSWI
function that the command has started. If OPOK is used, this response is given when
XLNPROXY receives the signal.
If no movement of the switch is registered within the limit
tStartMove
, the command is
considered failed, and the cause of the failure is evaluated. In the evaluation, the
function checks if the state of the represented switch is indicating that the command is
blocked in any way during the command, and gives the appropriate cause to the
SCSWI function. This cause is also shown on the output L_CAUSE as indicated in the
following table:
1MRK 505 370-UUS A
Section 12
Control
Busbar protection REB670 2.2 ANSI
351
Application manual
Summary of Contents for RELION REB670
Page 1: ...RELION 670 SERIES Busbar protection REB670 Version 2 2 ANSI Application manual ...
Page 2: ......
Page 24: ...18 ...
Page 40: ...34 ...
Page 72: ...66 ...
Page 102: ...96 ...
Page 266: ...260 ...
Page 272: ...266 ...
Page 290: ...284 ...
Page 432: ...426 ...
Page 542: ...536 ...
Page 552: ...546 ...
Page 553: ...547 ...