Figure 179:
Switchyard layout breaker-and-a-half
M13570-7 v4
Three types of interlocking modules per diameter are defined. BH_LINE_A (3) and
BH_LINE_B (3) are the connections from a line to a busbar. BH_CONN (3) is the
connection between the two lines of the diameter in the breaker-and-a-half switchyard
layout.
M13569-4 v4
For a breaker-and-a-half arrangement, the modules BH_LINE_A, BH_CONN and
BH_LINE_B must be used.
12.4.9.2
Configuration setting
M13569-6 v5
For application without 989 and 989G, just set the appropriate inputs to open state and
disregard the outputs. In the functional block diagram, 0 and 1 are designated
0=FALSE and 1=TRUE:
•
989_OP = 1
•
989_CL = 0
•
989G_OP = 1
•
989G_CL = 0