13.2
Logic for group alarm ALMCALH
GUID-64EA392C-950F-486C-8D96-6E7736B592BF v1
13.2.1
Identification
GUID-64EA392C-950F-486C-8D96-6E7736B592BF v1
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Logic for group alarm
ALMCALH
-
-
13.2.2
Application
GUID-70B268A9-B248-422D-9896-89FECFF80B75 v1
Group alarm logic function ALMCALH is used to route alarm signals to different
LEDs and/or output contacts on the IED.
ALMCALH output signal and the physical outputs allows the user to adapt the alarm
signal to physical tripping outputs according to the specific application needs.
13.2.3
Setting guidelines
GUID-0BDD898A-360B-4443-A5CF-7619C80A17F4 v2
Operation
:
Enabled
or
Disabled
13.3
Logic for group alarm WRNCALH
13.3.1
Identification
GUID-3EBD3D5B-F506-4557-88D7-DFC0BD21C690 v4
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Logic for group warning
WRNCALH
-
-
13.3.1.1
Application
GUID-FC0DBB7B-FF86-44BF-83D6-DDF120A176DE v1
Group warning logic function WRNCALH is used to route warning signals to LEDs
and/or output contacts on the IED.
WRNCALH output signal WARNING and the physical outputs allows the user to
adapt the warning signal to physical tripping outputs according to the specific
application needs.
Section 13
1MRK 505 370-UUS A
Logic
408
Busbar protection REB670 2.2 ANSI
Application manual
Summary of Contents for RELION REB670
Page 1: ...RELION 670 SERIES Busbar protection REB670 Version 2 2 ANSI Application manual ...
Page 2: ......
Page 24: ...18 ...
Page 40: ...34 ...
Page 72: ...66 ...
Page 102: ...96 ...
Page 266: ...260 ...
Page 272: ...266 ...
Page 290: ...284 ...
Page 432: ...426 ...
Page 542: ...536 ...
Page 552: ...546 ...
Page 553: ...547 ...