Configuration of inputs and outputs of PCFCNT is made via PCM600.
On the Binary input module (BIM), the debounce filter default time is set to 1 ms, that
is, the counter suppresses pulses with a pulse length less than 1 ms. The input
oscillation blocking frequency is preset to 40 Hz meaning that the counter detects the
input to oscillate if the input frequency is greater than 40 Hz. Oscillation suppression is
released at 30 Hz. Block/release values for oscillation can be changed on the local HMI
and PCM600 under
Main menu/Configuration/I/O modules
.
The setting is common for all input channels on BIM, that is, if limit
changes are made for inputs not connected to the pulse counter, the
setting also influences the inputs on the same board used for pulse
counting.
15.2
Function for energy calculation and demand handling
ETPMMTR
SEMOD153638-1 v2
15.2.1
Identification
SEMOD175537-2 v4
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Function for energy calculation and
demand handling
ETPMMTR
W_Varh
-
15.2.2
Application
SEMOD175546-4 v5
Energy calculation and demand handling function (ETPMMTR) is intended for
statistics of the forward and reverse active and reactive energy. It has a high accuracy
basically given by the measurements function (CVMMXN). This function has a site
calibration possibility to further increase the total accuracy.
The function is connected to the instantaneous outputs of (CVMMXN) as shown in
figure
.
Section 15
1MRK 505 370-UUS A
Metering
462
Busbar protection REB670 2.2 ANSI
Application manual
Summary of Contents for RELION REB670
Page 1: ...RELION 670 SERIES Busbar protection REB670 Version 2 2 ANSI Application manual ...
Page 2: ......
Page 24: ...18 ...
Page 40: ...34 ...
Page 72: ...66 ...
Page 102: ...96 ...
Page 266: ...260 ...
Page 272: ...266 ...
Page 290: ...284 ...
Page 432: ...426 ...
Page 542: ...536 ...
Page 552: ...546 ...
Page 553: ...547 ...