The selection of the time source is done via the corresponding setting.
It is possible to select more than one time source, in which case one is backup for the
other. The time synchronization source with the best calculated time-quality is
automatically selected. For instance, if both GPS and IRIG-B are selected and both
sources have the required accuracy, optical IRIG-B with IEEE1344 will be
automatically selected as the time synchronization source. Or if GPS and SNTP are
selected, when the GPS signal quality is bad, the IED will automatically choose SNTP
as the time-source.
If PTP is activated, the device with the best accuracy within the synchronizing group
will be selected as the source. For more information about PTP, see the Technical
manual.
IEEE 1588 (PTP)
PTP according to IEEE 1588-2008 and specifically its profile IEC/IEEE 61850-9-3 for
power utility automation is a synchronization method that can be used to maintain a
common time within a station. This time can be synchronized to the global time using,
for instance, a GPS receiver. If PTP is enabled on the IEDs and the switches that
connect the station are compatible with IEEE 1588, the station will become
synchronized to one common time with an accuracy of under 1us. Using an IED as a
boundary clock between several networks will keep 1us accuracy on three levels or
when using an HSR, 15 IEDs can be connected in a ring without losing a single
microsecond in accuracy.
20.13.2
Setting guidelines
IP15089-1 v3
All the parameters related to time are divided into two categories: System time and
Synchronization.
20.13.2.1
System time
M11348-119 v5
The time is set with years, month, day, hour, minute, second and millisecond.
20.13.2.2
Synchronization
M11348-143 v4
The setting parameters for the real-time clock with external time synchronization are
set via local HMI or PCM600. The path for Time Synchronization parameters on local
HMI is
Main menu/Configuration/Time/Synchronization
. The parameters are
categorized as Time Synchronization (TIMESYNCHGEN) and IRIG-B settings (IRIG-
B:1) in case that IRIG-B is used as the external time synchronization source.
1MRK 505 370-UUS A
Section 20
Basic IED functions
Busbar protection REB670 2.2 ANSI
519
Application manual
Summary of Contents for RELION REB670
Page 1: ...RELION 670 SERIES Busbar protection REB670 Version 2 2 ANSI Application manual ...
Page 2: ......
Page 24: ...18 ...
Page 40: ...34 ...
Page 72: ...66 ...
Page 102: ...96 ...
Page 266: ...260 ...
Page 272: ...266 ...
Page 290: ...284 ...
Page 432: ...426 ...
Page 542: ...536 ...
Page 552: ...546 ...
Page 553: ...547 ...