Maximum clock deviation <±50 ppm nominal, <±100 ppm operational
•
Jitter and Wander according to ITU-T G.823 and G.825
•
Buffer memory <250 μs, <100 μs asymmetric difference
•
Format.G 704 frame, structured etc.Format.
•
No CRC-check
Synchronization in PDH systems connected to SDH systems
•
Independent synchronization, asynchronous mapping
•
The actual SDH port must be set to allow transmission of the master clock from
the PDH-system via the SDH-system in transparent mode.
•
Maximum clock deviation <±50 ppm nominal, <±100 ppm operational
•
Jitter and Wander according to ITU-T G.823 and G.825
•
Buffer memory <100 μs
•
Format: Transparent
•
Maximum channel delay
•
Loop time <40 ms continuous (2 x 20 ms)
IED with echo synchronization of differential clock (without GPS clock)
•
Both channels must have the same route with maximum asymmetry of 0,2-0,5 ms,
depending on set sensitivity of the differential protection.
•
A fixed asymmetry can be compensated (setting of asymmetric delay in built in
HMI or the parameter setting tool PST).
IED with GPS clock
•
Independent of asymmetry.
1MRK 505 370-UUS A
Section 21
Requirements
Busbar protection REB670 2.2 ANSI
535
Application manual