IC-IB
IB-IA
IA-IC
2
3
4
ANSI11000028-2-en.vsd
SMAI_20
ANSI11000028 V2 EN-US
Figure 25:
Delta DAC connected three-phase CT set
In this case, everything is done in a similar way as in the above described example,
except that for all used current inputs on the TRM the following setting parameters
shall be entered:
CT
prim
=800A
CT
sec
=1A
•
CTWyePoint
=ToObject
•
ConnectionType
=
Ph-Ph
It is important to notice the references in SMAI. As inputs at
Ph-Ph
are expected to be
A-B, B-Crespectively C-A we need to tilt 180º by setting
ToObject
.
4.2.2.7
Example how to connect single-phase CT to the IED
SEMOD55055-431 v8
gives an example how to connect the single-phase CT to the IED. It gives an
overview of the required actions by the user in order to make this measurement
available to the built-in protection and control functions within the IED as well.
Section 4
1MRK 505 370-UUS A
Analog inputs
82
Busbar protection REB670 2.2 ANSI
Application manual