en04000283_ansi.vsd
ZA
2
1
10
ZB
2
1
10
BS
ANSI04000283 V1 EN-US
Figure 49:
Example of station without main CTs in the bus-section bay
In such case two separate zones can be maintained only while bus coupler breaker is
open. As soon as bus coupler breaker is going to be closed the zone interconnection
feature must be activated and complete busbars will be automatically protected with
just one differential zone.
Since there are no current transformer in the bus coupler bay, there is no need to
allocate internal bay function block for the bus coupler bay. However some additional
configuration logic is required to obtain automatic zone interconnection activation
when bus coupler breaker shall be closed. Example of such logic, is shown in Figure
for a two-zone differential protection application.
Section 6
1MRK 505 370-UUS A
Differential protection
126
Busbar protection REB670 2.2 ANSI
Application manual
Summary of Contents for RELION REB670
Page 1: ...RELION 670 SERIES Busbar protection REB670 Version 2 2 ANSI Application manual ...
Page 2: ......
Page 24: ...18 ...
Page 40: ...34 ...
Page 72: ...66 ...
Page 102: ...96 ...
Page 266: ...260 ...
Page 272: ...266 ...
Page 290: ...284 ...
Page 432: ...426 ...
Page 542: ...536 ...
Page 552: ...546 ...
Page 553: ...547 ...