Set the
EnaAbs
=
Absolute
Set the
RefSource
=
Set Value
SetValue
shall be set between -2000000000 to 2000000000
Similarly for signed comparison between input and setting
Set the
EnaAbs
=
Signed
Set the
RefSource
=
Set Value
SetValue
shall be set between -2000000000 to 2000000000
13.14
Comparator for real inputs - REALCOMP
13.14.1
Identification
GUID-0D68E846-5A15-4C2C-91A2-F81A74034E81 v1
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Comparator for real inputs
REALCOMP
Real<=>
13.14.2
Application
GUID-5F7B1683-9799-4D27-B333-B184F8861A5B v1
The function gives the possibility to monitor the level of real values in the system
relative to each other or to a fixed value. It is a basic arithmetic function that can be
used for monitoring, supervision, interlocking and other logics.
13.14.3
Setting guidelines
GUID-DE69FF5B-7D34-4A30-9060-214E98BFF798 v2
Setting procedure on the IED:
EnaAbs
: This setting is used to select the comparison type between signed and absolute
values.
•
Absolute
: Comparison is performed with absolute values of input and reference.
•
Signed
: Comparison is performed with signed values of input and reference.
RefSource
: This setting is used to select the reference source between input and setting
for comparison.
1MRK 505 370-UUS A
Section 13
Logic
Busbar protection REB670 2.2 ANSI
423
Application manual
Summary of Contents for RELION REB670
Page 1: ...RELION 670 SERIES Busbar protection REB670 Version 2 2 ANSI Application manual ...
Page 2: ......
Page 24: ...18 ...
Page 40: ...34 ...
Page 72: ...66 ...
Page 102: ...96 ...
Page 266: ...260 ...
Page 272: ...266 ...
Page 290: ...284 ...
Page 432: ...426 ...
Page 542: ...536 ...
Page 552: ...546 ...
Page 553: ...547 ...